What is the configuration setting for IO Server redundancy in Vijeo Citect 7.0 or later versions?

The configuration setting for IO Server redundancy in Vijeo Citect 7.0 or later versions is as tabulated below :

Define Cluster - Cluster1

Citect1:
 
Citect2:
 
IO Servers:
 
 
 
Server Name:
Cluster Name:
Network address
 
IOServer1
Cluster 1
Net_pri                             
Name:
Cluster Name:
 
 
IOServer2
Cluster 1
Net_sec


 
Network Address :
      
Network Address :
 
Name:
Address:
Net_Pri
192.168.100.101
(PC LAN card Address)
Name:
Address:
Net_sec
192.168.100.102
(PCLAN card Address)
Boards:
 
 
 
Server Name:
IOServer1
Server Name:
IOServer2
Board Name:
IOServer1_Board1
BoardName:
IOServer2_Board1
Board Type:
TCPIP
Board Type:
TCPIP
Address:
0
Address:
0
Ports:
 
 
 
Server Name:
IOServer1
Server Name:
IOServer2
Port Name:
Board1 _Port1
Port Name:
Board2_Port1
Board Name:
IOServer1 _Board1
Board Name:
IOServer2_Board1
Port Number:
Special Option
1
-I192.168.0.10 -P502 -T
Port Number:
Special Option
1
-I192.168.0.10 -P502 -T
IO Devices:
 
 
 
Server Name:
IOServer1
Server Name:
IOServer2
Name:
Device1
Name:
Redund_Device1
Number:
1
Number:
1
Address:
1
Address:
1
Protocol:
ModNet20
Protocol:
Modnet20
Port Name:
Board1 _Port1
Port Name:
Board2_Port1
StartUp Mode:
Primary
StartUp Mode:
StandBy

Note: IO Device Numbers must be the same for redundancy.

Computer Setup:

Citect1
Citect2
IO Server :
 
Project: <ProjectName>
Project: <ProjectName>
IOServer: IOServer1
IOServer: IOServer2
TCPIP
TCPIP
Was this helpful?
What can we do to improve the information ?